How a power failure alarm works, and why it cannot depend on mains
7 min read
A power failure alarm watches whether a supply is live and raises an alert the moment it is lost, then again when it returns. The detail that decides whether it is any use is simple: the alarm, and the path its alert takes, must keep working when the mains has gone. We supply complete power failure monitoring built that way: power failure sensors in ZARC tags, a ZARC Gateway with an optional battery backup, and the dashboard that sends the alert. This guide explains how a power failure alarm detects mains loss, what makes one dependable, where to fit it and what to do about UPS and generator backup.
01
How a power failure alarm works: what it detects
A power failure alarm answers one question: is the supply live? It senses the presence of voltage on the circuit it is connected to and reports a change of state when that voltage disappears and when it comes back. That is a different job from a power quality meter, which records voltage, current, harmonics and dips in detail. For most sites the question that matters after an outage is whether the power is on, when it went and when it returned, and a presence alarm answers it directly.
The restoration alert is as important as the loss alert. It closes the event, tells the people who were alerted that they can stand down, and gives the length of the outage. For a cold store, that length decides what happens to the stock. For a pumping station, it shows how long the wet well was filling with no pump running.
02
Why a power failure alarm must run on its own battery
An alarm powered from the supply it is watching fails at the same moment as the thing it is meant to report. That sounds obvious, but it catches out a lot of installations: a mains-powered alarm unit with no backup, a sensor that relies on a mains-powered hub, or an alert that depends on a broadband router in the same building. When the power goes, all of them go quiet together.
A dependable power failure alarm runs on its own battery, so it carries on reporting through the outage it is describing. The ZARC power failure tag is battery-powered for that reason, and runs for up to five years as standard on its cell.
03
The alert path has to survive the outage too
The alert still has to leave the site. If it travels over the building's own broadband, a site-wide power cut takes the router down and the alert never arrives. Landline auto-diallers have a growing version of the same problem as copper lines are withdrawn and replaced by digital lines that need mains power at the premises.
The fix is a separate path with its own power. A gateway on its own 4G connection, with internal battery backup, passes the alert on through a site-wide power cut. The dashboard then raises the alert and sends it by SMS or email to named people. Where an old dialler currently does this job, the changeover is covered in GSM alarm dialler replacement.
04
Where to fit it: building, circuit or single item
Where the alarm is connected decides which failures it can see. On the incoming supply to a building, it reports a power cut from the network. It will not see a tripped breaker on one circuit inside the building, because the incoming supply is still live.
On a single circuit, it reports anything that removes power from that circuit: a network outage, a tripped breaker, a blown fuse or someone switching it off. For equipment where an unseen loss of power is expensive, such as a freezer, a pump controller or a comms room, fit the alarm on the circuit that feeds it, close to the equipment.
On a three-phase supply, decide at survey whether you need to know about the loss of a single phase. Some three-phase equipment stops when one phase drops, while lighting and sockets on the other phases carry on, so the building looks normal. Our power failure tag works on single-phase and three-phase supplies, and the inputs are configured to suit.
05
UPS and generator backup
A UPS or standby generator changes what the alarm is for. A UPS takes over without a break, so the room carries on and nothing appears wrong until the batteries are exhausted. A generator starts automatically and the site may never notice the outage at all. In both cases the alert on mains loss is what tells someone that the site is now running on borrowed time, or on fuel.
Fit the power failure alarm upstream of the UPS or the changeover switch, so it sees the mains itself rather than the backed-up supply. Then add the backup equipment's own signals. UPS units and generator controllers usually have volt-free outputs for on battery, low battery, generator running and generator fault, and a dry contact tag reads those without modifying the equipment.
06
Who gets told, and what happens if nobody answers
A power failure alert is only useful if it reaches someone who can act. Name the people for each site, the order they are contacted in and how long the dashboard waits before escalating to the next person. Out-of-hours routing matters most, since that is when an unattended outage costs most.
Silence needs covering as well. Every tag should check in on a schedule, so a tag that stops reporting raises its own alert, and the gateway should raise a separate alert if it loses power itself. Without those two checks, a monitoring system that has stopped working looks exactly like a site where nothing has happened.
For estates where water and gas supplies need the same watch as power, see utility outage early warning. For server and comms rooms, the wider set of measurements is in what to monitor in a server room.
Where to go next
- Product
- Solution
- Solution
- Product
- Solution
FAQ
Frequently asked questions
How does a power failure alarm work?
It senses whether voltage is present on the circuit it is connected to, and reports a change of state when the supply is lost and again when it returns. The reading goes to a dashboard, which sends the alert by SMS or email to named people and records the start, end and length of each outage.
Does a power failure alarm need its own power?
Yes. An alarm powered from the supply it watches fails at the same moment as that supply. A dependable alarm runs on its own battery, and its alert travels over a connection with its own backup, such as a gateway on 4G with internal battery backup.
Can a power failure alarm send an SMS?
On our system the tag reports to the dashboard, and the dashboard sends the alert by SMS, email or both to the people you name, with escalation if nobody acknowledges it. The tag itself sends nothing to a phone.
Will it tell me when the power comes back?
Yes. Restoration is reported as its own event, which closes the alert and gives the length of the outage.
Should it go on the incoming supply or on one circuit?
On the incoming supply it reports network power cuts but not a tripped breaker inside the building. On a single circuit it reports anything that removes power from that circuit. For critical equipment such as a freezer, pump controller or comms room, fit it on the circuit that feeds that equipment.
Does it work on a three-phase supply?
Our power failure tag works on single-phase and three-phase supplies. Decide at survey whether the loss of a single phase needs its own alert, since some three-phase equipment stops when one phase drops.